Search results

1 – 2 of 2
Article
Publication date: 4 December 2023

Abdulbasit Almhafdy and Abdullah Mohammed Alsehail

This paper investigates the optimization of window design factors (WDFs) in hospital buildings, particularly in government hospitals within the arid climate of the Qassim region…

Abstract

Purpose

This paper investigates the optimization of window design factors (WDFs) in hospital buildings, particularly in government hospitals within the arid climate of the Qassim region, with the aim of achieving a better cooling load reduction. Continuous monitoring of the hospital ward section is crucial due to patients' needs, requiring optimal indoor air quality and cooling load.

Design/methodology/approach

The study identifies the optimal conditions for WDF design to mitigate cooling load, including window-to-wall ratio (WWR), window orientation (WO), room size and U-value (thermal properties), effectively reduce energy consumption in terms of sensible cooling load (MWh/m2) and comply with local codes. Data collection involved a smart weather station, while the Integrated Environmental Solution Virtual Environment (IESVE) software facilitated the simulation process.

Findings

Key findings reveal that larger patient rooms were about 40% more energy-efficient than smaller rooms. The northern orientation showed lower energy consumption, and specific WWRs and glazing U-values significantly affected energy loads. In an analysis of U-value changes in energy performance based on the Saudi Building Code (SBC), the presented values did not meet the minimum energy consumption standards. For a valid 40% WWR with a thermal permeability of 2.89, 0.181 MWh/m2 was consumed, while for an invalid 100% WWR with the same permeability but facing the north, 0.156 MWh/m2 was consumed, which is considered an invalid practice. It is vital to follow prescribed standards to ensure energy efficiency and avoid unnecessary costs.

Originality/value

Focus lies in emphasizing the significance of adhering to prescribed standards, such as SBC, to guarantee energy efficiency and prevent unwarranted expenses. Additionally, the authors highlight the crucial role of optimizing glazing properties and allocating the WWR appropriately to achieve energy-efficient building design, accounting for diverse orientations and climatic conditions.

Details

Smart and Sustainable Built Environment, vol. ahead-of-print no. ahead-of-print
Type: Research Article
ISSN: 2046-6099

Keywords

Article
Publication date: 26 June 2023

Sarah Nazari, Payam Keshavarz Mirza Mohammadi, Amirhosein Ghaffarianhoseini, Ali Ghaffarianhoseini, Dat Tien Doan and Abdulbasit Almhafdy

This paper aims to investigate the optimization of window and shading designs to reduce the building energy consumption of a standard office room while improving occupants'…

Abstract

Purpose

This paper aims to investigate the optimization of window and shading designs to reduce the building energy consumption of a standard office room while improving occupants' comfort in Tehran and Auckland.

Design/methodology/approach

The NSGA-II algorithm, as a multi-objective optimization method, is applied in this study. First, a comparison of the effects of each variable on all objectives in both cities is conducted. Afterwards, the optimal solutions and the most undesirable scenarios for each city are presented for architects and decision-makers to select or avoid.

Findings

The results indicate that, in both cities, the number of slats and their distance from the wall are the most influential variables for shading configurations. Additionally, occupants' thermal comfort in Auckland is much better than in Tehran, while the latter city can receive more daylight. Furthermore, the annual energy use in Tehran can be significantly reduced by using a proper shading device and window-to-wall ratio (WWR), while building energy consumption, especially heating, is negligible in Auckland.

Originality/value

To the best of the authors' knowledge, this is the first study that compares the differences in window and shading design between two cities, Tehran and Auckland, with similar latitudes but located in different hemispheres. The outcomes of this study can benefit two groups: firstly, architects and decision-makers can choose an appropriate WWR and shading to enhance building energy efficiency and occupants' comfort. Secondly, researchers who want to study window and shading systems can implement this approach for different climates.

Details

Smart and Sustainable Built Environment, vol. ahead-of-print no. ahead-of-print
Type: Research Article
ISSN: 2046-6099

Keywords

1 – 2 of 2